IMPORTANT TECHNICAL SPECIFICATIONS FOR
TRUE-ON-LINE UPS SYSTEMS

KVA/KW 30.0 KVA/ 40.0 KVA / 50.0 KVA / 60.0 KVA/
24.0 KW 32.0 KW 40.0 KW 48.0 KW
 
Technology
Design Double conversion Intelligent UPS, With built in Isolation Transformer
Latest Design Microcomputer-Chip based
Switching Frequency High Frequency Design ensures : §  • Low Switching Losses §  • Purity of Sine-Wave §  • Ultra-fast Transient Response Very Low Noise
Transient Response For 100% step load change output stays within ± 5% and recovers within ½ cycle
Wave Form Pure Sine Wave
Distortion §  • Total Harmonic Distortion less than 2% for linear load. §  • Total Harmonic Distortion less than 5% for non-linear load
Overload Rating §  • 100 % Continuous 150 % for 30 seconds
Inverter Efficiency Better than 90 %
Operating Temperature 0 to 50�C. 95 % R.H. (Maximum) Our UPS has passed Environmental – Test From Defence Laboratory of R&DE (Engineers), Dighi, Pune
Low Noise Less than or Equal to 45 dB (A) (Standarad) at 1.0 mtr.
Transfer Time Zero
Genset Compatability UPS System is fully Compatible to any type of Genset
Input/ Output
Wide Input Range §  • 355 V AC – 470 V AC (Three phase)
Frequiency 45 – 60 Hz
Accurate Output §  • 415 VAC ± 1.0 % (Three Phase)
Output Frequiency 50 Hz ± 0.1% (Crystal Controlled)
Output Power Factor 0.8 lagging to unity
Metering & Indication
Metering On-board Analog / LCD Panel Meter to Display following parameters §  • Output Voltage §  • Input Voltage
Indications §  • Mains/Charger ON §  • Inverter ON §  • System Over-load §  • Battery Under-Voltage §  • Output Under/Over Voltage
Protections §  • Output Over-Voltage §  • Output Overload. The same shall be effective only for the normal continuous operation. §  • Output Short Circuit §  • Battery Under � Voltage §  • Forced Air-cooling to protect electronic other components from overheating.
Alarm §  • Mains Fail (Musical Alarm) §  • Battery Low Warning (Musical Alarm)
Battery
Battery Charger §  • Charger is designed on Boost/Trickle (CCCV) §  • Principle to keep batteries in top condition. Uses High Frequency design to ensure long battery life
DC Voltage 324 / 360 VDC
Useful Options (At Extra Cost) §  • Servo-Voltage Stabilizer for use in by-pass mode §  • Synchronised/Asynchronised Inverter Configuration §  • Critical / Non-Critical Redundant UPS §  • Dual-Redundant (Hot Standby / Load Sharing) UPS Configuration §  • Scott � Connected Transformer for Single Phasing of Input AC Mains and stepping down the Mains Voltage from 415 V to 270 V AC in bypass mode (Recommended for 10.0 KVA UPS and above with 3-phase Input) (CCCV) §  • Computer Interface (RS-232) for Automatic Unattended Shutdown of file-server & Monitoring of Battery Status. Options available for Novell-LAN/NT-WINDOWS/SCO-UNIX/LINUX §  • Remote Control indications & Alarms Panel to control The UPS functions from a distance.